Lytron RC006: troubleshooting and error codes
The ServiceForge knowledge base holds 16 documented symptoms for the Lytron RC006, with 49 ranked causes, 20 diagnostic checks with test points and expected values, and 6 error codes. Each symptom below shows its causes and the first check; the rest is one connection away. Connect ServiceForge to your AI
Symptoms
Low coolant flow
Reduced coolant flow rate or flow alarm triggered
Ranked causes
- 1. Pump suction strainer clogged (positive displacement pumps) (common)
- 2. Low coolant level or empty reservoir (common)
- 3. Water filter dirty or clogged (common)
- 4. Pressure relief set too low (positive displacement and turbine pumps) (occasional)
- 5. Restriction in external coolant lines (occasional)
- 6. Pump overload has tripped (occasional)
- 7. Leaks in external piping (occasional)
- 8. Pump motor shaft bound or damaged (rare)
- 9. Damaged pump (rare)
- 10. Shutoff feature enabled in controller (occasional)
- 11. Low flow switch tripped (occasional)
Check reservoir coolant level
- Test point
- Reservoir fill mark
- Expected
- Coolant at full mark
2 more checks with pass and fail actions, 11 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Audible alarm stays on
Continuous audible alarm from chiller (Control Package II and III only)
Ranked causes
- 1. Low coolant level in reservoir (common)
- 2. Level switch stuck (occasional)
- 3. Level switch damaged (occasional)
- 4. Low temperature alarm setpoint too close to cooling setpoint (occasional)
- 5. High temperature alarm setpoint too close to cooling setpoint (occasional)
Check reservoir coolant level
- Test point
- Reservoir sight glass or fill mark
- Expected
- Coolant level at full mark
1 more check with pass and fail actions, 5 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Unit does not power on caution
Circuit breaker off or tripped; no power to unit keypad or display
Ranked causes
- 1. Unit not plugged in or power disconnected (common)
- 2. Circuit breaker in OFF position (common)
- 3. Low voltage to unit (occasional)
- 4. Fault shutoff enabled in controller (occasional)
- 5. Pump not primed (occasional)
Verify power cord connected
- Test point
- Power outlet and unit plug
- Expected
- Power outlet has 120V/240V AC as rated
2 more checks with pass and fail actions, 5 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Chiller shuts down during operation
System stops unexpectedly after running normally
Ranked causes
- 1. Low flow switch tripped (common)
- 2. Auto temperature alarm tripped - process fluid overtemp (common)
- 3. Temperature setpoint not set properly (occasional)
- 4. Shutoff feature enabled in controller for low coolant flow (occasional)
4 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Cooling insufficient or unit does not cool
System runs but does not cool adequately or cooling load not reduced
Ranked causes
- 1. Cooling load exceeds unit capacity (common)
- 2. Controller setpoint too high (common)
- 3. Condenser coil fouled with dust or debris (occasional)
- 4. High-pressure cutout tripped (RC030/RC045 water-cooled only) (occasional)
Verify controller setpoint temperature
- Test point
- Controller display or menu
- Expected
- Setpoint matches application requirement
1 more check with pass and fail actions, 4 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Noisy compressor during operation
Compressor produces excessive or abnormal noise while running
Ranked causes
- 1. Liquid refrigerant collected in compressor (long cool storage) (occasional)
- 2. Pump shaft seal damage (rare)
- 3. Excessive pressure drop in system (occasional)
3 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Pump motor overheats caution
Pump motor temperature elevated or motor shuts down from thermal overload
Ranked causes
- 1. Obstruction in pump head (common)
- 2. Low level in reservoir (common)
- 3. Improper voltage to system (occasional)
Check coolant level in reservoir
- Test point
- Reservoir sight glass or fill mark
- Expected
- Coolant level at full mark
1 more check with pass and fail actions, 3 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Excessive pressure in facility water (water-cooled units only) caution
Water inlet pressure exceeds normal limits on water-cooled models
Ranked causes
- 1. High-pressure cutout tripped (RC030/RC045 water-cooled only) (common)
- 2. Low voltage or wrong voltage to unit (occasional)
2 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Noisy pump motor
Pump motor produces excessive noise or grinding sounds
Ranked causes
- 1. Positive displacement pump worn out (occasional)
- 2. Improper voltage to system (occasional)
2 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Pump fails to prime caution
Pump does not displace air in housing, preventing fluid from being drawn in; centrifugal and turbine pumps are non-self priming
Ranked causes
- 1. Trapped air in pump housing and suction line (common)
- 2. Pump not primed before operation (common)
Verify priming valve is in open position (if equipped)
- Test point
- Pump priming valve located between pump discharge and tank top
- Expected
- Valve in open position
1 more check with pass and fail actions, 6 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Recirculating pressure too high caution
System pressure exceeds normal operating range
Ranked causes
- 1. Pressure drop through system too large (common)
- 2. Pump internal pressure relief set too high (occasional)
2 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Unit starts then shuts off shortly after caution
Unit begins operation but stops within seconds or minutes of startup
Ranked causes
- 1. Compressor internal overload tripped (common)
- 2. Low flow shutoff activated (common)
Wait for compressor overload reset
- Test point
- Unit restart attempt
- Expected
- Unit does not shut off within 5 minutes of restart
2 corrective actions and part numbers are in ServiceForge. Connect ServiceForge to your AI
Calibration: temperature offset adjustment
Adjust calibration offset for temperature reading accuracy on RC006 chiller display
Ranked causes
- 1. Temperature display requires calibration offset (common)
Enter customer menu
- Test point
- Control panel buttons
- Expected
- Display shows CAL option after scrolling
2 more checks with pass and fail actions, 2 corrective actions, and part numbers are in ServiceForge. Connect ServiceForge to your AI
Excessive noise on startup
Unit produces loud noise during initial startup phase
Ranked causes
- 1. Liquid refrigerant in compressor suction line (common)
Listen for noise reduction
- Test point
- System operation duration
- Expected
- Noise diminishes within 5 minutes of running
1 corrective action and part numbers are in ServiceForge. Connect ServiceForge to your AI
Temperature display dim at startup
LCD display appears dim or faint during initial power-on
Ranked causes
- 1. Normal startup behavior - display backlight ramping (common)
Monitor display brightness after power-on
- Test point
- LCD display
- Expected
- Display brightens to normal level within 5-10 seconds
1 corrective action and part numbers are in ServiceForge. Connect ServiceForge to your AI
Temperature display reads incorrectly
Digital display shows wrong or fluctuating temperature value
Ranked causes
- 1. Temperature offset incorrectly set (common)
1 corrective action and part numbers are in ServiceForge. Connect ServiceForge to your AI
Error codes
| Code | Meaning | Trigger | Severity |
|---|---|---|---|
Err 01 | Controller initialization error | Error in controller software initialization during power up | error |
Err 02 | RTD error | RTD resistance outside expected range; disconnect, damage, cut wire, short, or internal malfunction | error |
Err 03 | Controller operational error | Error in controller software while the chiller is running | error |
Err 04 | Low flow error | Low flow condition exists in the system | critical |
Err 05 | Remote start | Chiller has been turned off from the front panel while the remote start feature is enabled within the user menu | warning |
Err 07 | Auto temperature shutdown | Process fluid temperature is above the highest allowable temperature | critical |
Likely causes and actions for each code are in ServiceForge. Connect ServiceForge to your AI
Community
0 fixes logged by technicians through their AI, with outcomes, for this model.
ServiceForge knowledge base record. Field-unverified unless technicians confirmed it. A teaching summary of the record, not a service manual. Export 2026-10-14.